Main
Range of product
HDCX
Product or component type
Contactor
Contactor application
Motor control
Poles description
3P
Mechanical interlocking
Without mechanical interlock
Complementary
Utilisation category
AC-1
AC-2
AC-3
AC-4
AC-2
AC-3
AC-4
[In] rated current
25.0 A
Auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV
[Ie] rated operational current
25.0 A at 220/230 V AC-3
25.0 A at 380/400 V AC-3
18.0 A at 660/690 V AC-3
8.5 A at 220/230 V AC-4
8.5 A at 380/400 V AC-4
4.4 A at 660/690 V AC-4
25.0 A at 380/400 V AC-3
18.0 A at 660/690 V AC-3
8.5 A at 220/230 V AC-4
8.5 A at 380/400 V AC-4
4.4 A at 660/690 V AC-4
Motor power kW
5.5 kW at 220/230 V AC 50/60 Hz AC-3 for 3 phases motors
11.0 kW at 380/400 V AC 50/60 Hz AC-3
15.0 kW at 660/690 V AC 50/60 Hz AC-3
2.2 kW at 220/230 V AC 50/60 Hz AC-4
4.0 kW at 380/400 V AC 50/60 Hz AC-4
3.7 kW at 660/690 V AC 50/60 Hz AC-4
11.0 kW at 380/400 V AC 50/60 Hz AC-3
15.0 kW at 660/690 V AC 50/60 Hz AC-3
2.2 kW at 220/230 V AC 50/60 Hz AC-4
4.0 kW at 380/400 V AC 50/60 Hz AC-4
3.7 kW at 660/690 V AC 50/60 Hz AC-4
[Ith] conventional free air thermal current
40 A
Height
86.5 mm
Width
45.5 mm
Depth
103 mm
Product weight
0.595 kg
Environment
Installation category
III
Pollution degree
3
Ambient air temperature for operation
-5…40 °C
Average ambient air temperature for operation
<= 35 °C (average over 24 hours)
Ambient air temperature for storage
-25…55 °C
Operating altitude
2000 m
Standards
EN/IEC 60947-4-1
Product certifications
CE
CB
SEMKO
CB
SEMKO
Relative humidity
0…95 %
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Offer Sustainability
Sustainable packaging
No
| Language | Format | Size | Date |
|---|