Main
Range of product
HDB9LE
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Frame size
32AF
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Trip unit technology
Thermal-magnetic
Device application
Isolation
Complementary
Poles description
3P
[In] rated current
10 A
[Ue] rated operational voltage
400 V AC 50...60 Hz
Residual current
30 mA
[Uimp] rated impulse withstand voltage
4.0 kV
Curve code
C
Magnetic tripping limit
5...10 x In
Breaking capacity
6.0 kA
[Ui] rated insulation voltage
500 V
Protection type
Short-circuit protection
Overload protection
Earth-leakage protection
Residual current breaker with overcurrent protection (RCBO)
Overload protection
Earth-leakage protection
Residual current breaker with overcurrent protection (RCBO)
Cable entry
Top
Mounting support
35 mm DIN rail
Clamping connection capacity
<= 25 mm²
Tightening torque
2…3 N.m
Connections - terminals
Forked type tag connectors
Height
101 mm
Width
108.0 mm
Depth
78.5 mm
Environment
Tropicalisation
2
IP degree of protection
IP20
Electrical shock protection class
Class II
Ambient air temperature for operation
-30…70 °C
Standards
IEC 61009-1
Product certifications
CE
| Language | Format | Size | Date |
|---|