Main
Range of product
HJX2F 4P
Product or component type
Contactor
Contactor application
Non-reversing
Poles description
4P
[Uc] control circuit voltage
110 V AC 50/60 Hz
Mechanical interlocking
Without mechanical interlock
Complementary
[In] rated current
500 A
Auxiliary contact composition
4 NO
[Ui] rated insulation voltage
690 V
[Uimp] rated impulse withstand voltage
8 kV
[Ie] rated operational current
500 A at 440 V AC-3
147 A at 440 V AC-3
355 A at 660 V AC-4
145 A at 660 V AC-4
147 A at 440 V AC-3
355 A at 660 V AC-4
145 A at 660 V AC-4
Motor power kW
147 kW at 220/240 V AC 50/60 Hz AC-3 for 3 phases motors
250 kW at 380/400 V AC 50/60 Hz AC-3
280 kW at 415 V AC 50/60 Hz AC-3
280 kW at 440 V AC 50/60 Hz AC-3
335 kW at 500 V AC 50/60 Hz AC-3
355 kW at 660/690 V AC 50/60 Hz AC-3
335 kW at 1000 V AC 50/60 Hz AC-3
250 kW at 380/400 V AC 50/60 Hz AC-3
280 kW at 415 V AC 50/60 Hz AC-3
280 kW at 440 V AC 50/60 Hz AC-3
335 kW at 500 V AC 50/60 Hz AC-3
355 kW at 660/690 V AC 50/60 Hz AC-3
335 kW at 1000 V AC 50/60 Hz AC-3
[Ith] conventional free air thermal current
630 A
Environment
Installation category
III
Pollution degree
3
Ambient air temperature for operation
-5…40 °C
Average ambient air temperature for operation
<= 35 °C (average over 24 hours)
Ambient air temperature for storage
-25…55 °C
Operating altitude
2000 m
Standards
EN/IEC 60947-4-1
Product certifications
CE
IP degree of protection
IP20
Relative humidity
0…90 %
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Language | Format | Size | Date | |
---|---|---|---|---|
Catalog | ||||
English |
23.41 MB |
05/07/2023 |
Catalog

MOTOR CNTRL PROT CAT
pdf
English
23.41 MB
05/07/2023