Main
Range of product
HDW3
Product or component type
Air circuit breaker
Frame size
1600AF
[Icu] ultimate breaking capacity
35 kA at 690 V load
50 kA at 400 V load
50 kA at 400 V load
[Ics] rated service breaking capacity
35 kA at 690 V
42 kA at 400 V
42 kA at 400 V
[Icw] rated short-time withstand current
35 kA at 690 V duration: 1 s
42 kA at 400 V duration: 1 s
42 kA at 400 V duration: 1 s
Complementary
[In] rated current
1000 A
Poles description
4P
Mounting mode
Fixed
Mounting position
Horizontal
[Uc] control circuit voltage
230 V AC: motor mechanism (MCH) + closing release (XF)
230 V AC: shunt release (MX)
230 V AC: undervoltage release (MN)
230 V AC: shunt release (MX)
230 V AC: undervoltage release (MN)
Maximum tripping time
25 ms
Maximum closing response time
70 ms
Auxiliary contact composition
4 NO + 4 NC
Product compatibility
Series intelligent controller iTR326A standard protection
Height
310 mm
Width
346 mm
Depth
229 mm
Net weight
17 kg
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
31.0 cm
Package 1 Width
34.6 cm
Package 1 Length
22.9 cm
Package 1 Weight
17.0 kg
Language | Format | Size | Date | |
---|---|---|---|---|
User guide | ||||
English |
16.70 MB |
12/06/2020 |
||
English |
35.53 MB |
06/12/2021 |
||
Catalog | ||||
English |
61.92 MB |
28/08/2023 |
||
Certificate | ||||
English |
2.27 MB |
18/03/2019 |
||
English |
2.26 MB |
21/03/2019 |
||
CAD | ||||
English |
stp |
27.55 MB |
10/08/2021 |
|
English |
dwg |
0.13 MB |
04/08/2021 |
User guide

HDW3 ICU UM
pdf
English
16.70 MB
12/06/2020

HDW3 UM EN 2021-12-6 A0463040700HM
pdf
English
35.53 MB
06/12/2021
Catalog

HDW3-20230825
pdf
English
61.92 MB
28/08/2023
Certificate

HDW3 1600 3315373 01A
pdf
English
2.27 MB
18/03/2019

HDW3 1600 33 107809
pdf
English
2.26 MB
21/03/2019
CAD

HDW3 1600 4p Fix
English
stp
27.55 MB
10/08/2021

hdw3 1600 4p fix
English
dwg
0.13 MB
04/08/2021